Rated line-to-line voltage

The rated voltage of a cable is limited to the choices below. However, when laid in a project, the operating voltage of every cable system can be chosen arbitrary but no higher than $U_m$

For DC cables, e.g. in PV installations, the highest voltage of equipment is 1.5 · $U_m$ according to DIN VDE 0298-3.
$U_m$ will increase as follows: 440→660 V, 500→825 V, 825→1238 V, 1 kV→1.8 KV, 3 kV→5.4 kV.

Symbol
$U_n$
Unit
kV
Used in
Choices
$U_n$$U_m$$U_{mDC}$$U_0$Standard
208 V240 V 120 VUSA, Canada
400 V440 V660 V230 VDIN VDE 0298-3
480 V600 V 277 VUSA, Canada
500 V550 V825 V300 VDIN VDE 0298-3
750 V825 V1238 V450 VDIN VDE 0298-3
1 kV1.2 kV1.8 kV0.6 kVIEC 60502-1 Ed.2.1
3 kV3.6 kV5.4 kV1.8 kVIEC 60502-1 Ed.2.1
6 kV7.2 kV 3.6 kVIEC 60502-2 Ed.3.0
6.6 kV7.2 kV 3.8 kVHD 620 S2:2010 Part 1
10 kV12 kV 6 kVIEC 60502-2 Ed.3.0
11 kV12 kV 6.35 kVUK & Commonwealth
15 kV17.5 kV 8.7 kVIEC 60502-2 Ed.3.0
20 kV24 kV 12 kVIEC 60502-2 Ed.3.0
22 kV24 kV 12.7 kVHD 620 S2:2010 Part 1
25 kV30 kV 15 kVHD 620 S2:2010 Part 1
30 kV36 kV 18 kVIEC 60502-2 Ed.3.0
33 kV36 kV 19 kVUK & Commonwealth
36 kV42 kV 20.8 kVHD 620 S2:2010 Part 1
45 kV52 kV 26 kVIEC 60840 Ed.5.0
60 kV72.5 kV 36 kVIEC 60840 Ed.4.0
66 kV72.5 kV 38 kVUK & Commonwealth
110 kV123 kV 64 kVIEC 60840 Ed.5.0
132 kV145 kV 76 kVIEC 60840 Ed.5.0
150 kV170 kV 87 kVIEC 60840 Ed.5.0
220 kV245 kV 127 kVIEC 62067 Ed.3.0
275 kV300 kV 160 kVUK & Commonwealth
280 kV300 kV 160 kVIEC 62067 Ed.3.0
330 kV362 kV 190 kVIEC 62067 Ed.3.0
380 kV420 kV 220 kVIEC 62067 Ed.3.0
400 kV420 kV 230 kVUK & Commonwealth
500 kV550 kV 290 kVIEC 62067 Ed.3.0