Skin effect coefficient

Skin effect coefficient for Milliken conductors depending on insulation material and wire stranding orientation for copper conductors or number of segments for aluminium conductors. The skin effect in a single-core cable is substantially the same as the skin effect in a solid round cylindrical conductor having the same d.c. resistance per unit length.

Values are according to IEC 60287-1-1 with extensions from Cigre TB 272. Default value is $k_1$ = 1.0 for cases not covered below. Values for PP are assumed to be identical to PE and for SiR to EPR.

For hollow conductors, the formula from IEC 60287-1-1 Annex B should be used. This value is also applicable to keystone conductors.

Symbol
$k_s$
Formulas
$\frac{d_c-d_{ci}}{d_c+d_{ci}} \left(\frac{d_c+2d_{ci}}{d_c+d_{ci}}\right)^2$Hollow conductor
$\frac{D_c-D_{ci}}{D_c+D_{ci}} \left(\frac{D_c+2D_{ci}}{D_c+D_{ci}}\right)^2$conductor PAC/GIL
$\frac{D_{encl}-D_{encl}-2t_{encl}}{D_{encl}+D_{encl}-2t_{encl}} \left(\frac{D_{encl}+2\left(D_{encl}-2t_{encl}\right)}{D_{encl}+D_{encl}-2t_{encl}}\right)^2$enclosure PAC/GIL
Choices
$c_{type}$MaterialInsulationDirectionValue
3CuPEunidirectional0.62
3CuPEbidirectional0.8
3CuPEinsulated0.35
3CuHDPEunidirectional0.62
3CuHDPEbidirectional0.8
3CuHDPEinsulated0.35
3CuXLPEunidirectional0.62
3CuXLPEbidirectional0.8
3CuXLPEinsulated0.35
3CuXLPEfunidirectional0.62
3CuXLPEfbidirectional0.8
3CuXLPEfinsulated0.35
3CuPVCunidirectional0.62
3CuPVCbidirectional0.8
3CuPVCinsulated0.35
3CuEPRunidirectional0.62
3CuEPRbidirectional0.8
3CuEPRinsulated0.35
3CuIIRunidirectional0.62
3CuIIRbidirectional0.8
3CuIIRinsulated0.35
3CuPPunidirectional0.62
3CuPPbidirectional0.8
3CuPPinsulated0.35
3CuSiRunidirectional0.62
3CuSiRbidirectional0.8
3CuSiRinsulated0.35
3CuPPLP0.435
3CuMass0.435
3CuOilP0.435
3Al0.25
3Al4 segments0.288
3Al5 segments0.195
3Al6 segments0.118
3Al7 segments0.07
3AL30.25