Inclination derating factor

In the case of inclined ducts, it is important to consider that the methods for determining $T_4$. The IEC standards assume that a 1 m cable length equates to a 1 m length of ground surface for the heat to be dissipated from. This assumption is violated for inclined ducts, and the effect should be taken into account.

For example: in case of a 45 degrees inclined duct, then 1 m of cable equates to 0.71 m of ground surface, and hence, $T_4$ should be increased by a factor of 1.41.

Symbol
$F_{\alpha}$
Unit
p.u.
Formulae
$\frac{1}{cos\left(\frac{\alpha_{sys} \pi}{180}\right)}$