Mechanical force phase-to-phase fault

According to IEC 61914, Annex B.3

Symbol
$F_{k,2}$
Unit
kN/m
Formulas
$\alpha_{k,2} f_k {i_{p,2}}^2 \frac{1}{GMD_k} \frac{1}{1000}$IEC 61914
$\alpha_{k,2} \frac{\mu_0}{2\pi} \left(1000i_{p,2}\right)^2 \frac{1}{S_m} \frac{1}{1000}$Swissgrid Baukasten
Used in
$F_{k,max}$