Length corrugated sheath

The length of pitch of the corrugated sheath also plays a role, and should be taken into account when calculating the electrical resistance of the sheath.

Symbol
$L_{cor,sh}$
Unit
mm
Formulas
$\frac{0.25{L_{pitch}}^2+{H_{sh}}^2}{H_{sh}} \left(\\arcsin\left(\frac{L_{pitch} H_{sh}}{0.25{L_{pitch}}^2+{H_{sh}}^2}\right)+0\right)$
Related