Temperature coefficient of conductor material

Temperature coefficient of conductor material per K at 20°C Values are taken from standard IEC 60287-1-1 Ed.2.1 when available.

Value for Aldrey (AL3) is taken from diploma thesis 'Quantifying the effect of time and temperature on the mechanical behaviour of Aldrey overhead line conductors' by M. Frigerio, 2016.

Values for some other elements are:

Symbol
$\alpha_c$
Unit
1/K
Choices
MaterialValueReference
Cu0.00393IEC 60287-1-1
Al0.00403IEC 60287-1-1
AL30.004Manufacturer
Brz0.003IEC 60287-1-1
CuZn0.0019engineeringtoolbox.com
Ni0.00587engineeringtoolbox.com
SS0.001engineeringtoolbox.com