Extension to IEC 60287-2-1 for a single group.
| Id | Installation | Factor Zbs | Ebs | gbs | f | Info |
|---|---|---|---|---|---|---|
| 1 | 1 object | 0.21 | 3.94 | 0.6 | 1.0 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.3D |
| 2 | 2 objects touching, horizontal | 0.29 | 2.35 | 0.5 | 0.888 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.5D |
| 3 | 2 objects spaced, horizontal | 0.21 | 3.94 | 0.6 | 1.0 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.3D, hor. clearance ≥ 0.75D |
| 4 | 2 objects touching, vertical | 1.42 | 0.86 | 0.25 | 0.888 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.5D |
| 5 | 2 objects spaced, vertical | 0.75 | 2.8 | 0.3 | 1.0 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.5D, ver. clearance ≥ D |
| 6 | 3 objects touching, horizontal | 0.62 | 1.95 | 0.25 | 0.833 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.5D |
| 7 | 3 objects spaced, horizontal | 0.21 | 3.94 | 0.6 | 1.0 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.3D, hor. clearance ≥ 0.75D |
| 8 | 3 objects touching, vertical | 1.61 | 0.42 | 0.2 | 0.833 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ D |
| 9 | 3 objects spaced, vertical | 1.31 | 2.0 | 0.2 | 1.0 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.5D, ver. clearance ≥ D |
| 10 | 3 objects touching, trefoil | 0.96 | 1.25 | 0.2 | 0.667 | Installation on non-continuous brackets, ladder supports or cleats, clearance to wall ≥ 0.5D |
| 11 | 3 objects spaced, trefoil | 0.96 | 1.25 | 0.2 | 0.667 | Installation with separate clamps, clearance to wall ≥ 0.5D |