Installation on tray

According to IEC 60287-2-1 for a single group of cables and IEC 60287-2-2 for more than one group of cables. The wall clearance $e_{wall}$ is the distance between the closest cable to the wall and the object clearance $e_{hor}$ and $e_{ver}$ is the horizontal and vertical distance between two objects. Both values are relative to the outer diameter of the object.

Aditions to IEC 60287-2-1 have been made:

Symbol
$inst_{tray}$
Choices
IdInstallationFactor
Zbs

Ebs

gbs
Clearance
wall
objects
11 object0.213.940.60.30
22 objects touching, horizontal0.292.350.50.50
42 objects touching, vertical1.420.860.250.50
63 objects touching, horizontal0.621.950.250.50
103 objects touching trefoil0.961.250.20.50