Radius over capacitive insulation layers

This is the radius over all insulation layers up to the first metallic shielding layer.

For single-core cables, this is typically the radius of the insulation without the insulation screen (outer semi-conducting layer). In case of nulti-core cables screen, this is the radius from the center of the cable to the screen, sheath or armour.

Symbol
$r_{osc}$
Unit
mm
Formulas
$\frac{D_{ins}}{2}$single-core cables, with screen/sheath
$\frac{D_{ab}}{2}$single-core cables, without screen/sheath, with armour
$\frac{D_j}{2}$single-core cables, without screen/sheath, without armour
$\frac{D_{ins}}{2}$multi-core cables SC/SS or with, screen SS or with, sheath > 36 kV
$\frac{D_{scb}}{2}$belted cables (CC), with common screen
$\frac{D_f}{2}$belted cables (CC), no screen, with common sheath
$\frac{D_{scb}}{2}$belted cables (SC), with separate screen
$\frac{D_f}{2}+t_{ab,1}$belted cables (SC), no screen, with common sheath
$\frac{D_{scb}}{2}$belted cables (SS), with separate screen
$\frac{D_{scs}}{2}$belted cables (SS), no screen, with separate sheath
$\frac{D_f}{2}+t_{ab,1}$belted cables, no screen, no sheath, with armour
$\frac{D_j}{2}$belted cables, no screen, no sheath, without armour