Specific volumetric compression pressure insulation

Specific volumetric compression pressure on the insulation relative to the width of a clamp and the distance between two clamps. Permissible value for polymeric insulation materials is ≤ 6 N/mm$^3$.

Symbol
$\sigma_{clamp}$
Unit
N/mm$^3$
Formulas
$\frac{1000\operatorname{max}\left(F_{clamp}\right)}{t_i d_c d_{clamp}}$