For calculation of the cyclic and emergency current rating of cables acc. IEC 60853, the multi-core cable is replaced by an equivalent single-core construction dissipating the same total conductor losses. The space between the equivalent single-core conductor and the sheath is considered to be completely occupied by insulation. For oil-filled cables, this space is filled partly by the total volume of oil in the ducts and the remainder is oil-impregnated paper.
| $t_1$ | single-core cables |
| $\frac{D_{i,t}-d_{c,t}}{2}+t_{scb}+t_{scs}+\frac{H_{sh}+\Delta H}{2}$ | multi-core cables, type SS |
| $\frac{D_{i,t}-d_{c,t}}{2}+t_{scb}+t_{scs}+t_f+\frac{H_{sh}+\Delta H}{2}$ | multi-core cables, type SC |
| $\frac{D_{i,t}-d_{c,t}}{2}+t_f+t_{scb}+t_{scs}+\frac{H_{sh}+\Delta H}{2}$ | multi-core cables, type CC |
| $\frac{D_{i,t}-d_{c,t}}{2}+t_{scb}+t_{scs}+t_f$ | multi-core cables, without screen & sheath |
| $\frac{D_{i,t}-d_{c,t}}{2}+t_{scb}$ | pipe-type cables |