Induced shield voltage in phase b

The voltage gradient induced in a cable shield may be considered as a special case in which the parallel conductor is a shield at a spacing from the conductor that it embraces equal to the mean radius of the shield. When no other current-carrying conductor is in the vicinity.

Symbol
$E_b$
Unit
V/m
Formulae
$+j \omega I_{kb} 2{\cdot}{10}^{-7} \left(\frac{1}{2} \ln\left(\frac{4S_{ab} S_{bc}}{d^2}\right)+j \frac{\sqrt{3}}{2} \ln\left(\frac{S_{bc}}{S_{ab}}\right)\right)$three-phase symmetrical fault, general case, without transposition
$+j \omega I_{kb} 2{\cdot}{10}^{-7} \ln\left(\frac{2S_m}{d}\right)$three-phase symmetrical fault, trefoil, without transposition
$+j \omega I_{kb} 2{\cdot}{10}^{-7} \ln\left(\frac{2S_m}{d}\right)$three-phase symmetrical fault, flat, without transposition
$+j \omega I_{ka} 2{\cdot}{10}^{-7} \ln\left(\frac{GMD}{d}\right)$three-phase symmetrical fault, with regular transposition
$-j \omega I_{ka} 2{\cdot}{10}^{-7} \ln\left(\frac{2S_{ab}}{d}\right)$phase-to-phase fault between phases a + b
$I_{kc} \left(R_{ct}+j \omega 2{\cdot}{10}^{-7} \ln\left(\frac{S_{ap} S_{bp}}{r_g S_{ab}}\right)\right)$single-phase ground fault in phase a, single-side bonded (solidly grounded neutral)
$+j \omega I_{kb} 2{\cdot}{10}^{-7} \ln\left(\left(\frac{S_m}{d}\right)^2 \frac{d}{r_g}\right)$highest single-phase ground fault in phase a, single-side bonded (without Rct)
$\frac{I_{kx}}{3} \left(Z_{ss}+2Z_{sg}\right)-I_{kb} Z_{sg}$single-phase ground fault in phase a minor section 1, cross-bonded, trefoil
$\frac{I_{kx}}{3} \left(Z_{ss}-2Z_{oig}\right)-I_{kb} Z_{oig}$single-phase ground fault in phase a minor section 1, cross-bonded, flat
$\frac{I_{kb}}{2} \left(R_{ct}+j \omega 2{\cdot}{10}^{-7} \ln\left(\frac{D_E}{S_{ab}}\right)\right)$single-phase ground fault in phase a, single-side bonded (without ecc)