Absorption coefficient solar radiation

The absorption coefficient of solar radiation for the cable surface is used to calculate the temperature rise due to solar radiation.

The coefficient is material-dependant, typical values are given in standard IEC 60287-1-1 for different cable jacket materials and in standard IEC 60287-2-1 for different duct materials.

No reference values were found for Polypropylene (PP), Silicone rubber (SiR) and Chlorosulphonated polyethylene (CSM) and they are assumed to be similar to PVC.

Symbol
$\sigma_{sun}$
Choices
CodeCableDuctTrayMaterial
PE0.40.40.4Polyethylene (LD/MDPE, ST3)
HDPE0.40.4-High density polyethylene (HDPE, ST7)
XLPE0.40.4-Crosslinked polyethylene (XLPE)
PVC0.60.60.6Polyvinyl chloride (PVC, ST1/2)
PP0.60.6-Polypropylene (PP)
PPY0.60.6-Polypropylene yarn (PP)
FRNC0.80.4-Flame-Retardant Non-Corrosive polyethylene (FRNC)
HFS0.40.4-HFS-110-TP (AS/NZS 3808:2000 R2016)
POC0.6--Polyolefin copolymer (POC)
SiR0.6--Silicone rubber (SiR)
CR0.8--Polychloroprene (CR, Neoprene)
CSM0.6--Chlorosulphonated polyethylene (Hypalon)
CJ0.8--Compounded jute
RSP0.8--Rubber sandwich protection
BIT0.80.8-PVC/bitumen tapes
WPE-0.4-duct made of plastic filled with water
Metal-0.2-duct made of steel
Alu--0.1tray made of aluminum
StN--0.64tray made of galvanized steel (new)
StW--0.8tray made of galvanized steel (weathered)
Fibre-0.60.6duct made of fibrous material (glass-reinforced plastic, GRP)
Cem-0.70.75duct made of cement
Earth-0.75-duct made of earthenware (vitrified clay, VCP)