Voltage levels in Cableizer

Cableizer does currently support AC voltage levels from medium voltages of 1 kV up to extra-high voltages of 500 kV. DC voltage levels are currently limited to below 5 kV. For low-voltage cable sizing, alternatives to Cableizer are readily available.

Posted 2014-11-05
Categories: Theory


For a comprehensive overview of supported rated cable voltages in Cableizer, including their corresponding highest equipment voltages, test voltages, and IEC standards coverage, refer to the documentation about the rated cable voltage.

In Cableizer, voltage levels are categorized according to the following table:

Low voltagesLV$U_m$ <= 1 kV
Medium voltagesMV1 kV < $U_m$ <= 52 kV
High voltagesHV52 kV < $U_m$ <= 245 kV
Extra-high voltagesEHV245 kV < $U_m$ <= 800 kV
Ultra-high voltagesUHV$U_m$ > 800 kV

Cableizer support following voltage levels

Rated phase-to-phase voltage
$U_n$
Highest voltage for equipment
$U_m$
Operating voltage
$U_0$
Relevant standard
 
400 V440 V230 VDIN VDE 0298-3
500 V550 V300 VDIN VDE 0298-3
750 V825 V450 VDIN VDE 0298-3
1 kV1.2 kV0.6 kVIEC 60502-1 Ed.2.1
3 kV3.6 kV1.8 kVIEC 60502-1 Ed.2.1
6 kV7.2 kV3.6 kVIEC 60502-2 Ed.3.0
10 kV12 kV6 kVIEC 60502-2 Ed.3.0
15 kV17.5 kV8.7 kVIEC 60502-2 Ed.3.0
20 kV24 kV12 kVIEC 60502-2 Ed.3.0
30 kV36 kV18 kVIEC 60502-2 Ed.3.0
45 kV52 kV26 kVIEC 60840 Ed.4.0
60 kV72.5 kV36 kVIEC 60840 Ed.4.0
110 kV123 kV64 kVIEC 60840 Ed.4.0
132 kV145 kV76 kVIEC 60840 Ed.4.0
150 kV170 kV87 kVIEC 60840 Ed.4.0
220 kV245 kV127 kVIEC 62067 Ed.2.0
280 kV300 kV160 kVIEC 62067 Ed.2.0
330 kV362 kV190 kVIEC 62067 Ed.2.0
380 kV420 kV220 kVIEC 62067 Ed.2.0
500 kV550 kV290 kVIEC 62067 Ed.2.0

For the sizing of low-voltage cables according to NEC electrical code on House Wiring or similar standards from IEC or VDE, there exists a free online software called Cablesizer (not affiliated with Cableizer).